What are Anti Condensation Heaters (ACH)?

Anti Condensation Heaters (or ACH) are heating devices used to protect electric motors against condensation when motors are installed in damp or wet conditions or conditions where condensation may occur. ACH must be energised when the motor is not running and de-energised when the motor is running.

ACH are not fitted as standard, but are available as a additional retro fit option by request.

A separate terminal block is usually provided for the heater connections.

Usually the rated voltage is either 110Vac or 230Vac.

Total power is not normally critical and standard ACH units may be fitted on industrial motors over a wide range of supply voltages.

220V Heater bands (wire colour orange)

Motor Frame SizeTypeLength (mm)WattsResistance (min-max Ω)
8000b20385200-6655
900b305251670-2110
1001b432261615-2008
1122b686212059-2555
132-1603b686401110-1299
180-2004b762261671-1972
225-2505b1016421075-1256
2807b147365710-792
3158b170299444-520

110V Heater bands (wire colour black)

Motor Frame SizeTypeLength (mm)WattsResistance (min-max Ω)
8000a20381360-1663
900a30522478-582
1001a43227407-488
1122a68621530-621
132-1603a68640275-325
180-2004a76225455-505
225-2505a101639284-336
2807a147367172-192
3158a1702103109-122

For motors not having the provision of space heaters, 24 V dc supply can be applied between any two terminals.